FIR - Cu:Mica:XLPE:CTS:LSZH

FIR – Cu/Mica/XLPE/CTS/LSZH
0.6/1kV

Control cable, fire resistant, low smoke zero halogen (LSZH), XLPE insulated, screened

Standards: IEC 60502-1; IEC 60331; IEC 60227

Construction: Cu/Mica/XLPE/CTS/LSZH

  1. Conductor: Plain annealed copper (class 2)
  2. Fire barrier: Mica tape
  3. Insulation: XLPE
  4. Filler & binder (if any)
  5. Screen: copper tape
  6. Outer sheath: LSZH

Cable identification:

  • Cores:
    • 2 cores: By numeral on black insulation
      • More than 2 cores: By numeral on black insulation except green-yellow core (if any)
  • Outer sheath: orange or as order

Characteristics:

  • Voltage rate: 0.6/1kV
  • Maximum conductor temperature: 900C in normal operation; 2500C in short-circuit for 5s max.
  • Minimum bend radius: 8xD (eight times overall diamerter of cable)
  • Fire resistant: IEC 60331
  • Flame retardant: IEC 60332-1
  • Acid gas emission (HCl): IEC 60502-1; IEC 60754-1
  • Smoke emission: IEC 61034-2

 

APPLICATION:


Gas station, elevator, tunnel…

Airfield, building, apartment

Public place

Fire alarm systems, lighting security systems,

System of fire extinguishing electric pumps…

Standard: IEC 60331 IEC 60332 BS 6387, BS 7211…

Voltage level up to 0.6/1 kV

 