CVV
0.6/1kV
Power cable, four-cores with reduced neutral conductor, compacted copper conductor, PVC insulated, unarmoured, sheathed
Standards: TCVN 5935, IEC 60502-1
Construction: Cu/PVC/PVC
- Conductor: Annealed plain copper (class 2, compacted circular)
- Insulation: PVC
- Filler: PVC or PP; binder tape (if any)
- Outer sheath: PVC (ST1 type)
Cable identification: by color of PVC insulation
- Phase cores: Red, yellow, blue
- Neutral core: Black
- Outer sheath: Black
The above identifying can be changed as order
Characteristics:
- Rated voltage (Uo/U): 0.6/1kV
- Max. conductor temperature in normal operation: 70oC
- Max. conductor temperature in short-circuit for 5s max duration:
- Conductor cross-section > 300 mm2: 1400C
- Conductor cross-section ≤ 300 mm2: 1600C
- Min. bend radius: 8 x D (D: overall diameter of cable)
APPLICATION:
Laid on cable ladder, tray, in duct in a thermal insulated wall, on a wall or spaced from wall, on the dry and closed cable trench in workshops, building; from source to machine or device, in duct in the ground…