chong-chay-FIH trungtinh
FIH trungtinhchong-chay-FIH trungtinh-01chong-chay-FIH trungtinh-02

FLH – Cu/XLPE/LSZH/DSTA/LSZH
0.6/1kV

Low smoke zero halogen (LSZH) Flame retardant cable, 2, 3, 4-cores, XLPE insulated,  armoured (double of steel tape), sheathed

 

Standards: IEC 60502-1; IEC 60332

Construction: Cu/XLPE/LSZH/DSTA/LSZH

  1. Conductor: Plain annealed copper (class 2, normal stranded or compact stranded)
  2. Insulation: XLPE
  3. Filler, binder and inner covering: PP, PET, LSZH
  4. Armour: Double of steel tape
  5. Outer sheath: LSZH

Cable identification:

  • Cores: by color tape
  • Outer sheath: Orange or as order

Characteristics:

  • Voltage rate: 0.6/1kV
  • Maximum conductor temperature: 900C in normal operation; 2500C in short-circuit for 5s max.
  • Minimum bend radius: 12xD (twelve times overall diamerter of cable)
  • Flame retardant: IEC 60332-1; IEC 60332-3-24
  • Acid gas emission (HCl): IEC 60502-1; IEC 60754-1
  • Fluorine content: IEC 60502-1; IEC 60684-2
  • pH and conductivity: IEC 60502-1; IEC 60754-2
  • Smoke emission: IEC 61034-2

 

 

APPLICATION:


Gas station, elevator, tunnel…

Airfield, building, apartment

Public place

Fire alarm systems, lighting security systems,

System of fire extinguishing electric pumps…

Standard: IEC 60331 IEC 60332 BS 6387, BS 7211…

Voltage level up to 0.6/1 kV

 

TECHNICAL INFORMATION OF PRODUCTS: